| 1000 CFM (138 m/3H)-5000 CFM (8460 m/3H) |
| |
| Specifications |
| |
Series CFM
( m ³ /m) |
Approximate Dimensions
H x W x L, inches
(H x W x L, cm)
|
Nominal Power
Volts, Phase, Amps |
Approximate Weight, lbs. |
| 1,000 (23 m³) |
30 x 42 x 52
(76 x 107 x 132 cm) |
480V, 3 Ø , 26 A (MAX)
25KW |
350 (159Kg) |
| 2,000 (56m³) |
44 x 52 x 100
(112 x 132 x 254 cm) |
480V, 3 Ø , 35 A (MAX)
30KW |
1,080 (491Kg) |
| 3,000
(85m³) |
44 x 52 x 100
(112 x 132 x 254 cm) |
480V, 3 Ø , 57 A (MAX)
40KW |
1,325
(602Kg) |
| 3,500
(99m³) |
45 x 78 x 118
(114 x 198 x 300 cm) |
480V, 3 Ø , 60 A (MAX)
50KW |
1,760
(800Kg) |
| 5,000
(141m³) |
51 x 78 x 118
(130 x 198 x 300 cm) |
480V, 3 Ø , 100 A (MAX)
67KW |
2,100
(955Kg) |
|
|
|
| |
| |
| |
| 20 |
27 |
| 30 |
40 |
| 40 |
52 |
| 50 |
65 |
| 60 |
77 |
| 75 |
96 |
| 100 |
124 |
| |
|
|
| |
| Job site power sources that are already in place for pumps, motors, mixers, etc., may be connected to the dehumidification equipment. |
|
| |
| Calculating using Ambient Conditions of 70 - 77 °F |
(17.8 - .25°C) and 50-60% Relative Humidity |
CFM
M³/M M³/hr |
1,000 (23) (1380) |
2,000 (56) (3360) |
3,000 (85) (5100) |
3,500 (99) (5940) |
5,000 (141) (8460) |
DH Only
amps
|
>24 ° F
>13.3 °C
26 |
>15 °F
>8.3 °C
35 |
>39 °F
>21.5 °C
57 |
>18 °F
>10 °C
60 |
>24 °F
>13.3 °C
100 |
Mod. DH
amps |
0 °F
0 °C
25 |
|
>7 °F
>3.9 °C
31 |
|
>5 °F
>2.8 °C
67 |
A/C Only
amps |
<16 ° F
<8.8 °C 6 |
<22 °F <12.2 °C
10 |
<20 °F
<11.1 °C
10 |
<20 °F
<11.1 °C
15 |
<26 °F
<14.4 °C
30 |
Heat
Only
amps |
>35 ° F
>22.0 °C
20 |
>37 °F >20.4 °C
25 |
>55 °F
>30.3 °C
47 |
>38 °F
>20.9 °C
45 |
>50 °F
>27.5 °C
70 |
Internal
Heaters |
15KW |
20KW |
30KW |
36KW |
54KW |
|
| |
| > Greater than ambient |
|
|
| |
| |
|
| |
|
 |
|